Skip to content Skip to footer

Borri efficiency without compromise

Electrical Review Logo

Borri is the driving power behind data centre efficiency

Uninterruptible power supply (UPS) systems form the foundation of a data centre’s electrical infrastructure and provide physical ‘insurance policies’, protecting the safe operation of the computing layer. It is therefore vital that operators are not blinded by the drive for greater efficiency and remember the primary purpose of the UPS system – ultimate power protection.

Dedicated to traditional UPS design, Borri knows conventional UPS systems operating in true online double conversion mode (VFI),provide the highest level of protection. However, Borri warns historically this type of configuration leads to a poor level of efficiency especially when sized conservatively for a data centre application and these efficiency figures can take a further drop when multiple UPS units are used in parallel for resilience and redundancy, taking the maximum loading to 50% of total capacity.

 

To combat these poor efficiency levels, many UPS systems now comewith an ECO option, or a direct line mode of operation (typically VI orVFD), this bypasses the online double conversion technology and allowspower to directly flow from input to output. This configuration significantly increases efficiency levels but also cuts the protective nature of the UPS.

Where once this function was used for non-sensitive loads such as emergency lighting systems which are not really affected by a short power break, misguidedly, some data centres are now using the ECO mode as a standard setting, to save power.

 

Compromised protection?

Taking efficiency even further, many of these ECO functions have resulted in the increased intelligence of UPS solutions, enabling them to automatically select which mode of operation to choose, subject to mains voltage conditions, historical data, and even the weather. Some manufacturers are even employing these ECO modes as the standard operation to increase UPS efficiency with a minority even removing the ability for data centre managers to manually change the settings in preparation for even a planned power cut!

These new ECO technologies can now achieve efficiency levels of 95-98%. This is a substantial increase when compared to conventional online double conversion UPS, but Borri is keen to point out that operating in any substandard form of ECO mode is subject to a very significant compromise in protection, as the UPS becomes a reactionary device and puts the data centre at risk. Any modern UPS which operates as a default in this way (VI or VFD) of operation has to react to any issue with the mains supply, it may well react within a few milliseconds, but those few milliseconds can easily compromise the safe operation of the computing layer supported by the UPS, the very reason the original investment in the UPS was made.

Conventional online double conversion UPS solutions are unable to achieve the same efficiency levels, but they do provide a constant output to the load that is isolated from mains input protecting the connected equipment from all mains borne disturbances, and therefore delivers far superior power protection.

However, Borri believes data centre managers should not have to choose between high efficiency with compromised protection, or complete protection with compromised efficiency and after extensive research and development, has developed a portfolio of UPS systems that provide the best of both worlds.

Ultimate protection

Available from 60kVA upwards, Borri’s UPS units are of traditional design and incorporate online double conversion topology. They also include an output isolation transformer as standard to provide ultimate protection,due to galvanic isolation of the critical load from input spikes, surges, inverter switching devices and DC voltages.

Investing at component level ensures that users gain maximum power protection by operating in online double conversion mode but can also achieve high efficiency levels. These sophisticated UPS solutions from Borri can operate at efficiencies of 95% at full load, and even over 93% at half load and below, ensuring users deploying the units in redundancy can still achieve impressive efficiency gains.

Not content with this, the latest FXS upgrade in 2011, has added the option for Smart Online (SOL) mode, giving control to the user and the option to allow the UPS to switch between conditioned line and direct line mode of operation.

The company’s dedication to delivering power protection solutions that are not only reliable but which can also achieve high efficiency levels has led to the development of a range of ultra-efficient UPS systems.

Exclusively developed by Borri S.p.A, the innovative B9000FXS and B9600FXS series incorporates Smart OnLine technology (SOL), which cleverly monitors the quality of power supplied, and chooses the most efficient operating mode based on the environmental conditions at thetime and can achieve efficiency levels of up to 99 percent.

Unlike other UPS systems, SOL allows the user to select how and when it is to operate in a high-efficiency, direct line mode. The system will always revert to a conditioned line mode as default, until an operator defines the characteristics to run in high-efficiency direct line mode, giving the user total control.

Importantly, data centre operators can take full control, consideration can now be given to the power output, day-to-day energy consumption and environmental impact, as the FXS upgrade gives data centre operators the flexibility as to whether they operate in Online Double Conversion (VFI) for complete protection or run Smart Online mode for even higher efficiency. The flexibility of the system allows for this decision to be constantly reviewed and changed as required by the data centre.

Ongoing commitment

Borri’s ongoing commitment to efficiency has earned its UPS systems from 60kVA to 6.4MVA a place on the Governments Energy Technology List (Part of the Enhanced Capital Allowance Scheme). The ETL List provides users with, not only a list of the most efficient technologies/products available but also offers significant tax incentives to those users who invest in products which are listed.

Efficiency without compromise…

Achieve the best of both worlds: Ultimate power protection and high efficiency

As a full turnkey solutions provider Borri offers:

 

·         UPS Systems from 800VA to 6.4MVA ECA ETL UPS systems from 60kVA to 6.4MVA

·         Standby generators

·         Service and maintenance

·         Battery replacements

·         Electrical installations

·         Energy efficiency audits

·         Site surveys

·     To find out more about Borri’s high efficiency UPS systems please call:

Tel: 0800 136 993 or Email: [email protected] www.borri.co.uk

 

 

You may also like

Stay In The Know

Get the Electrical Review Newsletter direct to your inbox, and don't miss a thing.